Exciter Model: EXDC2_PTI
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.25*Mult*TimeStep then Tr = 0.0
ElseIf 0.25*Mult*TimeStep < Tr < 0.5*Mult*TimeStep then Tr = 0.5*Mult*TimeStep - If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0 < Tf1 < Mult*TimeStep then Tf1 = Mult*TimeStep
- If Vrmax < Vrmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
Model Equations and/or Block Diagrams
Parameters:
| Tr | Filter time constant, sec |
| Ka | Voltage regulator gain |
| Ta | Time constant, sec |
| Tb | Lag time constant, sec |
| Tc | Lead time constant, sec |
| Vrmax | Maximum control element output, pu |
| Vrmin | Minimum control element output, pu |
| Ke | Exciter field resistance line slope margin, pu |
| Te | Exciter time constant, sec |
| Kf | Rate feedback gain, pu |
| Tf1 | Rate feedback time constant, sec |
| Switch | Parameter not used in PowerWorld |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |